SUPER THERMAL-RESISTANT ALUMINUM-ALLOY CONDUCTORS,ALUMINUM-CLAD INVAR REINFORCED
SUPER THERMAL-RESISTANT ALUMINUM-ALLOY CONDUCTORS,ALUMINUM-CLAD INVAR REINFORCED

STACIR/AW,Hi-STACIR/AW SUPER THERMAL-RESISTANT ALUMINUM-ALLOY CONDUCTORS,ALUMINUM-CLAD INVAR REINFORCED

The STACIR/AW (Hi-STACIR/AW) conductor is a new type of overhead conductor,consists of an aluminum-clad Invar core and heat-resistant aluminum alloy wires, which is suitable for the reconstruction of old lines to increase capacity while keeping the sag unchanged.
Quote Now
Share :
Application
STACIR/AW, Hi-STACIR/AW is normally used to up-rate an existing transmission line by simply replacing the existing conductor without tower modification or reinforcement.

Description 
Super thermal-resistant aluminum alloy conductor,aluminum clad Invar reinforced is a high ampacity conductor with inner core composed of aluminum clad Invar/high tensile strength aluminum-clad Invar& outer layer composed of super thermal-resistant aluminium alloy with round.


Chaircteritics
Double current carrying capacity of the same size ACSR
No limitation for application area : Heavy wind, snow & galloping area
Equivalent Sag-tension properties to conventional ACSR
No modification & reinforcement on existing tower
Easy installation with same method & equipments as ACSR's
Low cost and short construction period 

Specification
IEC,ASTM,JCS 1405
 
High reliability
Super high pressure
Less maintenance
Technical Parameter
Conductor
Size
Calculated Area
Stranding
Overall
Diameter
Approx.Weight Min.
Breaking
Load
DC Resistance
 at 20℃
STAL AL-INVAR Total STAL AL-INVAR STAL AL-INVAR Total
mm² mm² mm² mm² No./mm No./mm mm kg/km kg/km kg/km kgf Ω/km
160 159.30 37.16 196.46 30/2.6 7/2.6 18.20 441.7 265.2 706.9 6140 0.1745
240 241.30 56.29 297.59 30/3.2 7/3.2 22.40 669.1 401.7 1070.8 9170 0.1159
330 326.80 52.84 379.64 26/4.0 7/3.1 25.30 905.1 377.0 1282.1 10000 0.0869
410 413.40 67.35 480.75 26/4.5 7/3.5 28.50 1145.5 480.6 1626.1 12720 0.0686
480
(Rail)
483.84 33.54 517.38 45/3.7 7/2.47 29.61 1340.7 239.3 1580.0 10500 0.0600
480
(Cardinal)
484.52 62.81 547.33 54/3.38 7/3.38 30.42 1343.5 452.2 1795.7 13280 0.0591
Conductor
Size
Calculated Area
Stranding
Overall
Diameter
Approx.Weight Min.
Breaking
Load
DC Resistance
 at 20℃
STAL HI-AL-INVAR Total STAL HI-AL-INVAR STAL HI-AL-INVAR Total
mm² mm² mm² mm² No./mm No./mm mm kg/km kg/km kg/km kgf Ω/km
160 159.30 37.16 196.46 30/2.6 7/2.6 18.20 441.7 265.2 706.9 6500 0.1745
240 241.30 56.29 297.59 30/3.2 7/3.2 22.40 669.1 401.7 1070.8 9700 0.1159
330 326.80 52.84 379.64 26/4.0 7/3.1 25.30 905.1 377.0 1282.1 10500 0.0869
410 413.40 67.35 480.75 26/4.5 7/3.5 28.50 1145.5 480.6 1626.1 13300 0.0686
480
(Rail)
483.84 33.54 517.38 45/3.7 7/2.47 29.61 1340.7 239.3 1580.0 11000 0.0600
480
(Cardinal)
484.52 62.81 547.33 54/3.38 7/3.38 30.42 1343.5 452.2 1795.7 13800 0.0591



For more product details, please download our PDF files.