Medium Voltage Cables UNE HD 620 S3
Medium Voltage Cables UNE HD 620 S3

Medium Voltage Cables UNE HD 620 S3

Quote Now
Share :
Application
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.

Construction
● Conductor: Aluminum or copper, class 2,circular compacted conductors
● Conductor screen: Non-metallic,semi-conducting compound
● Insulation: Cross - Linked Polyethylene XLPE,Nominal Insulation Thickness or Reduced Insulation Thickness
● Insulation screen: Non-metallic,semi-conducting compound
● Metallic screen: Aluminium plastic tape (AL/PET)
● Outer sheath: Polyolefin,PO (DMZ1,DMZ2,LSOH,LSZH),Black or Red

Chaircteritics
Good electrical and mechanical properties. Low factor dielectric loss, high insulation resistance. The PO outer sheath allows adequate resistance to UV and abrasion.
Different CPR levels require different structures and materials.

Specification
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1 kV (Um=1.2kV) up to 30kV (Um=36kV) - Part 2:Cables for Rated Voltages of 6kV (Um=7.2kV) and 30 kV (Um=36kV)
HD 620 S1 Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2) kV to 20.8/36(42) kV
HD 620 S2 Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2) kV to 20.8/36(42) kV
UNE 211620 Cables eléctricos de distribución con aislamiento extruido, de tensión asignada desde 3.6/6 (7.2) kV hasta 20.8/36 (42) kV inclusive Cables unipolares y unipolares reunidos con aislamiento de XLPE Cables con pantalla de tubo de aluminio y cubierta de compuesto de poliolefina (tipos 10E-6, 10E-7, 10E-8 y 10E-9)
 
High reliability
Super high pressure
Less maintenance
POWER CABLE RH5Z1
No. of Cores and Nominal Cross Section Nominal Insulation Thickness  Nominal AL/PET
 tape thickness
Nominal
Sheath Thickness
Approx. Overall Diameter Approx. Weight Max. D.C. Resistance of Conductor at 20℃
Al Al
mm²  mm mm mm mm kg/km Ω/km
12/20kV Reduced Insulation Thickness
1X50 4.9 0.3 2.75 28.1 817 0.641
1X95 4.9 0.3 2.75 31.6 1067 0.320
1X150 4.9 0.3 2.75 34.3 1298 0.206
1X185 4.9 0.3 2.75 36.0 1456 0.164
1X240 4.9 0.3 2.75 38.3 1693 0.125
1X400 4.9 0.3 2.75 43.2 2263 0.0778
1X630 4.9 0.3 2.75 50.3 3191 0.0469
18/30kV Reduced Insulation Thickness
1X50 7.25 0.3 2.75 32.8 1055 0.641
1X95 7.25 0.3 2.75 36.3 1329 0.320
1X150 7.25 0.3 2.75 39.0 1579 0.206
1X185 7.25 0.3 2.75 40.7 1748 0.164
1X240 7.25 0.3 2.75 43.0 2001 0.125
1X400 7.25 0.3 2.75 47.9 2604 0.0778
1X630 7.25 0.3 2.75 55.0 3582 0.0469