600V Service Cable
600V Service Cable

600V Service Cable

The cables used at voltages of 600 volts and at conductor temperatures not to exceed 70°C for polyethylene (PE) and Polyvinyl chloride (PVC) insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.
Quote Now
Share :
APPLICATION
The cables used at voltages of 600 volts and at conductor temperatures not to exceed 70°C for polyethylene (PE) and Polyvinyl chloride (PVC) insulated conductors or 90°C for cross-linked polyethylene (XLPE) insulated conductors.

Construction
• Conductor:Copper/Aluminum/8000 series Aluminum Alloy/Copper clad Aluminum
• Insulation: XLPE/PVC/PE
•Concentric Neutral:Copper/Aluminum/8000 series Aluminum Alloy/Copper clad Aluminum
• Sheath: PVC/XLPE/PE

SPECIFICATIONS
• SANS 1507-6 Electric cables with extruded solid dielectric insulation for fixed installations (300/500 V to 1 900/3 300 V)  Part 6: Service cables 
• UL44 Standard For Safety Thermoset-Insulated Wires and Cables
• UL854 Standard For Safety Service-Entrance Cables
•PIESA 1062 Concentric Single-Phase Aerial Service Cable - For Domestic Service Connections With a Combined Neutral-Earth Conductor
•IEC 60502-1 Power Cables With Extruded Insulation And Their Accessories For Rated Voltages From 1 kV (Um = 1.2 kV) Up To 30 kV (Um = 36 kV) –Part 1: Cables For Rated Voltages Of 1 kV (Um = 1.2 kV) And 3 kV (Um = 3.6 kV) 
•KS 04-1022 Kenya Standard Specification For 600/1000V PVC-Insulated Single-Phase Concentric Cables With Copper Or Aluminum Conductors For Electricity Supply
High reliability
Super high pressure
Less maintenance
Technical Parameter
AAAC-8000/XLPE/UV-XLPE
Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.14 - 25 0.653 0.10 1.14 9.6 3.4464
2 × #6 7 1.555 1.14 - 25 0.813 0.10 1.14 11.1 2.1684
2 × #4 7 1.961 1.14 - 26 1.024 0.10 1.14 12.7 1.3633
3 × #6 7 1.56 1.14 1.0 65 0.511 0.10 1.52 13.5×20.4 2.1684
3 × #4 7 1.961 1.14 1.0 65 0.643 0.10 2.03 16.0×24.1 1.3633
3 × #2 7 2.474 1.14 1.0 65 0.813 0.10 2.03 17.8×27.5 0.8573
4 × #4 7 1.961 1.14 1.0 65 0.643 0.10 1.52 24.4 1.3633
4 × #2 7 2.474 1.14 1.0 65 0.813 0.10 2.03 29.1 0.8573
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath

 
AAAC-8000/XLPE/UV-PVC
Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.52 - 14 0.873 0.09 1.52 11.7 3.4464
3 × #6 7 1.555 1.52 1.0 20 1.070 0.09 1.52 13.5×20.4 2.1684
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath

CU/XLPE/UV-PVC 
Size Phase conductor Inner sheath* Neutral conductor Polyester tape Outer sheath Approx.
Overall dia.
Nominal D.C resistance at 20℃
No. of wire Dia. of wire Nominal
Insulation thickness
Nominal thickness No. of wire Dia. of wire Nominal thickness Nominal thickness
No. / AWG No. mm mm mm No. mm mm mm mm Ω/km
2 × #8 7 1.234 1.14 - 25 0.653 0.09 1.14 9.6 2.10
3 × #8 7 1.234 1.14 1.0 65 0.405 0.09 1.14 15×19 2.10
3 × #6 7 1.555 1.14 1.0 65 0.511 0.09 1.52 16×20 1.32
3 × #4 7 1.961 1.14 1.0 65 0.643 0.09 1.52 18×22 0.830
*:Two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath  
Aluminum/PVC/UV-PVC
Size Phase conductor Neutral
conductor
Polyester tape Outer sheath Approx.
Overall dia.
Ma.D.C resistance at 20℃
Size No. of wire Nominal
Insulation thickness
Size Nominal thickness Nominal thickness
Phase Neutral
Communication
No. / mm2 mm2 No. mm mm2 mm mm mm Ω/km Ω/km
1×10+23 10 7 1.55 23 0.05 1.4 12.21 3.08 1.335
1×16+26 16 7 1.55 26 0.05 1.4 13.34 1.91 1.808
1×25+29 25 7 1.60 29 0.05 1.5 14.88 1.20 1.0586
1×35+38.6 35 19 1.65 38.6 0.05 1.6 16.75 0.868 0.7966
CU/XLPE/UV-PE 
Size Phase conductor Neutral
Conductor Size
Concentric wires Polyester tape Outer sheath Approx.
Overall dia.
Ma.D.C resistance at 20℃
Size No. of wire Nominal
Insulation thickness
No. of cores Dia. of wire Nominal thickness Nominal thickness
Phase Neutral Communication
No. / mm2 mm2 No. mm mm2 No. mm mm mm mm Ω/km Ω/km Ω/km
2×4 4 7 0.7 4 2 0.8 0.05 1.4 10.2 4.75 4.61 35
2×6 6 7 0.7 6 2 0.8 0.05 1.4 10.8 3.18 3.08 35
2×10 10 7 0.7 10 2 0.8 0.05 1.4 12.0 1.89 1.83 35
2×16 16 7 0.7 16 2 0.8 0.05 1.4 13.0 1.19 1.15 35
4*×4 4 7 0.7 4 2 0.8 0.05 1.6 15.0 4.75 4.61 35
4*×6 6 7 0.7 6 2 0.8 0.05 1.6 16.5 3.18 3.08 35
4*×10 10 7 0.7 10 2 0.8 0.05 1.6 18.5 1.89 1.83 35
4*×16 16 7 0.7 16 2 0.8 0.05 1.6 21.0 1.19 1.15 35
Note:
  1. phase conductor shall be hard drawn copper;
  2. Neutral conductor shall be annealed copper and insulated or non-insulated as required;
  3. Concentric wires shall be annealed copper and insulated;
  4. *:Inner sheath of multi-core cable,two options based on client requirement, a) wrapping tape b) extrusion PVC inner sheath;  